CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 2470 kg
The Dynamic load for:
50 repetitions/day: 1820 kg
100 repetitions/day: 1680 kg
200 repetitions/day: 1505 kg
300 repetitions/day: 1395 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 2708 kg
The Dynamic load for:
50 repetitions/day: 1975 kg
100 repetitions/day: 1825 kg
200 repetitions/day: 1635 kg
300 repetitions/day: 1515 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 2600 kg
The Dynamic load for:
50 repetitions/day: 1900 kg
100 repetitions/day: 1770 kg
200 repetitions/day: 1568 kg
300 repetitions/day: 1455 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m4
Depth of cut joint: 4 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 2850 kg
The Dynamic load for:
50 repetitions/day: 2050 kg
100 repetitions/day: 1905 kg
200 repetitions/day: 1710 kg
300 repetitions/day: 1585 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m4
Depth of cut joint: 4 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 2850 kg
The Dynamic load for:
50 repetitions/day: 2085 kg
100 repetitions/day: 1925 kg
200 repetitions/day: 1725 kg
300 repetitions/day: 1600 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 3040 kg
The Dynamic load for:
50 repetitions/day: 2265 kg
100 repetitions/day: 2095 kg
200 repetitions/day: 1875 kg
300 repetitions/day: 1735 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 3000 kg
The Dynamic load for:
50 repetitions/day: 2180 kg
100 repetitions/day: 2020 kg
200 repetitions/day: 1830 kg
300 repetitions/day: 1670 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m4
Depth of cut joint: 4 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 3200 kg
The Dynamic load for:
50 repetitions/day: 2355 kg
100 repetitions/day: 2180 kg
200 repetitions/day: 1965 kg
300 repetitions/day: 1818 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m4
Depth of cut joint: 4 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 3230 kg
The Dynamic load for:
50 repetitions/day: 2370 kg
100 repetitions/day: 2190 kg
200 repetitions/day: 1960 kg
300 repetitions/day: 1815 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m - 4m
Outdoor slab: 2,5m - 3,5m
Depth of cut joint: 4,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 3600 kg
The Dynamic load for:
50 repetitions/day: 2575 kg
100 repetitions/day: 2375 kg
200 repetitions/day: 2130 kg
300 repetitions/day: 1975 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m - 4m
Outdoor slab: 2,5m - 3,5m
Depth of cut joint: 4,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 3400 kg
The Dynamic load for:
50 repetitions/day: 2480 kg
100 repetitions/day: 3000 kg
200 repetitions/day: 2045 kg
300 repetitions/day: 1920 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m - 4m
Outdoor slab: 2,5m - 3,5m4,5
Depth of cut joint: 4,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 3600 kg
The Dynamic load for:
50 repetitions/day: 2575 kg
100 repetitions/day: 2375 kg
200 repetitions/day: 2130 kg
300 repetitions/day: 1975 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m - 4m
Outdoor slab: 2,5m - 3,5m4,5
Depth of cut joint: 4,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 3610 kg
The Dynamic load for:
50 repetitions/day: 2675 kg
100 repetitions/day: 2465 kg
200 repetitions/day: 2210 kg
300 repetitions/day: 2045 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 3900 kg
The Dynamic load for:
50 repetitions/day: 2900 kg
100 repetitions/day: 2680 kg
200 repetitions/day: 2400 kg
300 repetitions/day: 2225 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 3800 kg
The Dynamic load for:
50 repetitions/day: 2800 kg
100 repetitions/day: 2580 kg
200 repetitions/day: 2325 kg
300 repetitions/day: 2145 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m5
Depth of cut joint: 5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4010 kg
The Dynamic load for:
50 repetitions/day: 3025 kg
100 repetitions/day: 2810 kg
200 repetitions/day: 2015 kg
300 repetitions/day: 2330 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m5
Depth of cut joint: 5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4050 kg
The Dynamic load for:
50 repetitions/day: 3000 kg
100 repetitions/day: 2760 kg
200 repetitions/day: 2470 kg
300 repetitions/day: 2290 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4300 kg
The Dynamic load for:
50 repetitions/day: 3245 kg
100 repetitions/day: 3000 kg
200 repetitions/day: 2685 kg
300 repetitions/day: 2490 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4260 kg
The Dynamic load for:
50 repetitions/day: 3140 kg
100 repetitions/day: 2930 kg
200 repetitions/day: 2590 kg
300 repetitions/day: 2420 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m5
Depth of cut joint: 5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4450 kg
The Dynamic load for:
50 repetitions/day: 3400 kg
100 repetitions/day: 3148 kg
200 repetitions/day: 2804 kg
300 repetitions/day: 2620 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m5
Depth of cut joint: 5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4500 kg
The Dynamic load for:
50 repetitions/day: 3320 kg
100 repetitions/day: 3070 kg
200 repetitions/day: 2750 kg
300 repetitions/day: 2540 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4800 kg
The Dynamic load for:
50 repetitions/day: 3610 kg
100 repetitions/day: 3330 kg
200 repetitions/day: 2985 kg
300 repetitions/day: 2765 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4700 kg
The Dynamic load for:
50 repetitions/day: 3490 kg
100 repetitions/day: 3200 kg
200 repetitions/day: 2890 kg
300 repetitions/day: 2660 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m5,5
Depth of cut joint: 5,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5000 kg
The Dynamic load for:
50 repetitions/day: 3765 kg
100 repetitions/day: 3490 kg
200 repetitions/day: 3106 kg
300 repetitions/day: 2896 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m5,5
Depth of cut joint: 5,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4950 kg
The Dynamic load for:
50 repetitions/day: 3675 kg
100 repetitions/day: 3390 kg
200 repetitions/day: 3035 kg
300 repetitions/day: 2810 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 6 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5200 kg
The Dynamic load for:
50 repetitions/day: 3990 kg
100 repetitions/day: 3685 kg
200 repetitions/day: 3300 kg
300 repetitions/day: 3055 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 6 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4900 kg
The Dynamic load for:
50 repetitions/day: 3840 kg
100 repetitions/day: 3562 kg
200 repetitions/day: 3180 kg
300 repetitions/day: 2960 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m6
Depth of cut joint: 6 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5420 kg
The Dynamic load for:
50 repetitions/day: 4184 kg
100 repetitions/day: 3860 kg
200 repetitions/day: 3468 kg
300 repetitions/day: 3170 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m6
Depth of cut joint: 6 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5450 kg
The Dynamic load for:
50 repetitions/day: 4040 kg
100 repetitions/day: 3725 kg
200 repetitions/day: 3340 kg
300 repetitions/day: 3100 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5800 kg
The Dynamic load for:
50 repetitions/day: 4390 kg
100 repetitions/day: 4050 kg
200 repetitions/day: 3625 kg
300 repetitions/day: 3365 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5700 kg
The Dynamic load for:
50 repetitions/day: 4220 kg
100 repetitions/day: 3900 kg
200 repetitions/day: 3500 kg
300 repetitions/day: 3245 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m6
Depth of cut joint: 6 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6000 kg
The Dynamic load for:
50 repetitions/day: 4600 kg
100 repetitions/day: 4220 kg
200 repetitions/day: 3780 kg
300 repetitions/day: 3510 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m6
Depth of cut joint: 6 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6475 kg
The Dynamic load for:
50 repetitions/day: 4420 kg
100 repetitions/day: 4100 kg
200 repetitions/day: 3660 kg
300 repetitions/day: 3390 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6300 kg
The Dynamic load for:
50 repetitions/day: 4800 kg
100 repetitions/day: 4440 kg
200 repetitions/day: 3975 kg
300 repetitions/day: 3680 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6750 kg
The Dynamic load for:
50 repetitions/day: 4625 kg
100 repetitions/day: 4300 kg
200 repetitions/day: 3820 kg
300 repetitions/day: 3550 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m6,5
Depth of cut joint: 6,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6500 kg
The Dynamic load for:
50 repetitions/day: 5035 kg
100 repetitions/day: 4658 kg
200 repetitions/day: 4160 kg
300 repetitions/day: 3840 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m6,5
Depth of cut joint: 6,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6500 kg
The Dynamic load for:
50 repetitions/day: 4830 kg
100 repetitions/day: 4450 kg
200 repetitions/day: 4000 kg
300 repetitions/day: 3700 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4m - 5m
Depth of cut joint: 7 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6850 kg
The Dynamic load for:
50 repetitions/day: 5240 kg
100 repetitions/day: 4840 kg
200 repetitions/day: 4330 kg
300 repetitions/day: 4020 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4m - 5m
Depth of cut joint: 7 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6750 kg
The Dynamic load for:
50 repetitions/day: 5060 kg
100 repetitions/day: 4670 kg
200 repetitions/day: 4212 kg
300 repetitions/day: 3870 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4m - 5m7
Depth of cut joint: 7 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 7000 kg
The Dynamic load for:
50 repetitions/day: 5480 kg
100 repetitions/day: 5065 kg
200 repetitions/day: 4540 kg
300 repetitions/day: 4230 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4m - 5m7
Depth of cut joint: 7 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6800 kg
The Dynamic load for:
50 repetitions/day: 5235 kg
100 repetitions/day: 4840 kg
200 repetitions/day: 4340 kg
300 repetitions/day: 4020 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 7400 kg
The Dynamic load for:
50 repetitions/day: 5700 kg
100 repetitions/day: 5260 kg
200 repetitions/day: 4710 kg
300 repetitions/day: 4360 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6800 kg
The Dynamic load for:
50 repetitions/day: 5490 kg
100 repetitions/day: 5090 kg
200 repetitions/day: 4560 kg
300 repetitions/day: 4230 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4,5m - 6m7
Depth of cut joint: 7 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 7700 kg
The Dynamic load for:
50 repetitions/day: 5950 kg
100 repetitions/day: 5505 kg
200 repetitions/day: 4940 kg
300 repetitions/day: 4565 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4,5m - 6m7
Depth of cut joint: 7 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 7600 kg
The Dynamic load for:
50 repetitions/day: 5670 kg
100 repetitions/day: 5240 kg
200 repetitions/day: 4690 kg
300 repetitions/day: 4350 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 8000 kg
The Dynamic load for:
50 repetitions/day: 6160 kg
100 repetitions/day: 5700 kg
200 repetitions/day: 5100 kg
300 repetitions/day: 4720 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 7850 kg
The Dynamic load for:
50 repetitions/day: 5950 kg
100 repetitions/day: 5510 kg
200 repetitions/day: 4900 kg
300 repetitions/day: 4560 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m7,5
Depth of cut joint: 7,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 8300 kg
The Dynamic load for:
50 repetitions/day: 6450 kg
100 repetitions/day: 5974 kg
200 repetitions/day: 5347 kg
300 repetitions/day: 4950 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m7,5
Depth of cut joint: 7,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 8250 kg
The Dynamic load for:
50 repetitions/day: 6120 kg
100 repetitions/day: 5660 kg
200 repetitions/day: 5060 kg
300 repetitions/day: 4700 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 8 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 8800 kg
The Dynamic load for:
50 repetitions/day: 6650 kg
100 repetitions/day: 6150 kg
200 repetitions/day: 5500 kg
300 repetitions/day: 5100 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 8 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 8552 kg
The Dynamic load for:
50 repetitions/day: 6400 kg
100 repetitions/day: 5905 kg
200 repetitions/day: 5300 kg
300 repetitions/day: 4912 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 8 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 9200 kg
The Dynamic load for:
50 repetitions/day: 6980 kg
100 repetitions/day: 6450 kg
200 repetitions/day: 5780 kg
300 repetitions/day: 5370 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 8 cm