CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 1995 kg
The Dynamic load for:
50 repetitions/day: 1500 kg
100 repetitions/day: 1400 kg
200 repetitions/day: 1250 kg
300 repetitions/day: 1150 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 2090 kg
The Dynamic load for:
50 repetitions/day: 1620 kg
100 repetitions/day: 1500 kg
200 repetitions/day: 1340 kg
300 repetitions/day: 1245 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m – 3,5m
Outdoor slab: 2m – 3 m
Depth of cut joint: 4 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 2100 kg
The Dynamic load for:
50 repetitions/day: 1575 kg
100 repetitions/day: 1470 kg
200 repetitions/day: 1300 kg
300 repetitions/day: 1220 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 2200 kg
The Dynamic load for:
50 repetitions/day: 1705 kg
100 repetitions/day: 1562 kg
200 repetitions/day: 1400 kg
300 repetitions/day: 1302 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m – 3,5m
Outdoor slab: 2m – 3 m
Depth of cut joint: 4 cm

 

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 2280 kg
The Dynamic load for:
50 repetitions/day: 1750 kg
100 repetitions/day: 1600 kg
200 repetitions/day: 1430 kg
300 repetitions/day: 1330 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 2423 kg
The Dynamic load for:
50 repetitions/day: 1875 kg
100 repetitions/day: 1730 kg
200 repetitions/day: 1550 kg
300 repetitions/day: 1435 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m – 3,5m
Outdoor slab: 2m – 3 m
Depth of cut joint: 4 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 2400 kg
The Dynamic load for:
50 repetitions/day: 1840 kg
100 repetitions/day: 1680 kg
200 repetitions/day: 1370 kg
300 repetitions/day: 1290 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 2550 kg
The Dynamic load for:
50 repetitions/day: 1960 kg
100 repetitions/day: 1802 kg
200 repetitions/day: 1630 kg
300 repetitions/day: 1512 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m – 3,5m
Outdoor slab: 2m – 3 m
Depth of cut joint: 4 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 2565 kg
The Dynamic load for:
50 repetitions/day: 1980 kg
100 repetitions/day: 1830 kg
200 repetitions/day: 1650 kg
300 repetitions/day: 1520 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m - 4m
Outdoor slab: 2,5m - 3,5m
Depth of cut joint: 4,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 2755 kg
The Dynamic load for:
50 repetitions/day: 2135 kg
100 repetitions/day: 1980 kg
200 repetitions/day: 1775 kg
300 repetitions/day: 1645 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m – 4m
Outdoor slab: 2,5m – 3,5m
Depth of cut joint: 4,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 2700 kg
The Dynamic load for:
50 repetitions/day: 2070 kg
100 repetitions/day: 1932 kg
200 repetitions/day: 1728 kg
300 repetitions/day: 1590 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m - 4m
Outdoor slab: 2,5m - 3,5m
Depth of cut joint: 4,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 2900 kg
The Dynamic load for:
50 repetitions/day: 2245 kg
100 repetitions/day: 2175 kg
200 repetitions/day: 1853 kg
300 repetitions/day: 1720 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m – 4m
Outdoor slab: 2,5m – 3,5m
Depth of cut joint: 4,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 2850 kg
The Dynamic load for:
50 repetitions/day: 2250 kg
100 repetitions/day: 2100 kg
200 repetitions/day: 1860 kg
300 repetitions/day: 1720 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m - 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 3040 kg
The Dynamic load for:
50 repetitions/day: 2430 kg
100 repetitions/day: 2245 kg
200 repetitions/day: 2010 kg
300 repetitions/day: 1865 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m – 4,5m
Outdoor slab: 3,5m – 4m
Depth of cut joint: 5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 3000 kg
The Dynamic load for:
50 repetitions/day: 2350 kg
100 repetitions/day: 2200 kg
200 repetitions/day: 1950 kg
300 repetitions/day: 1805 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m - 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 3200 kg
The Dynamic load for:
50 repetitions/day: 2555 kg
100 repetitions/day: 2352 kg
200 repetitions/day: 2113 kg
300 repetitions/day: 1950 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m – 4,5m
Outdoor slab: 3,5m – 4m
Depth of cut joint: 5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 3230 kg
The Dynamic load for:
50 repetitions/day: 2530 kg
100 repetitions/day: 2340 kg
200 repetitions/day: 2090 kg
300 repetitions/day: 1940 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m - 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 3420 kg
The Dynamic load for:
50 repetitions/day: 2735 kg
100 repetitions/day: 2528 kg
200 repetitions/day: 2265 kg
300 repetitions/day: 2095 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m – 4,5m
Outdoor slab: 3,5m – 4m
Depth of cut joint: 5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 3400 kg
The Dynamic load for:
50 repetitions/day: 2630 kg
100 repetitions/day: 2450 kg
200 repetitions/day: 2200 kg
300 repetitions/day: 2030 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m - 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 3600 kg
The Dynamic load for:
50 repetitions/day: 2870 kg
100 repetitions/day: 2662 kg
200 repetitions/day: 2372 kg
300 repetitions/day: 2185 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m – 4,5m
Outdoor slab: 3,5m – 4m
Depth of cut joint: 5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 3610 kg
The Dynamic load for:
50 repetitions/day: 2830 kg
100 repetitions/day: 2620 kg
200 repetitions/day: 2335 kg
300 repetitions/day: 2165 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 3800 kg
The Dynamic load for:
50 repetitions/day: 3060 kg
100 repetitions/day: 2820 kg
200 repetitions/day: 2525 kg
300 repetitions/day: 2345 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m – 5m
Outdoor slab: 3,5m – 4m
Depth of cut joint: 5,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 3800 kg
The Dynamic load for:
50 repetitions/day: 2950 kg
100 repetitions/day: 2740 kg
200 repetitions/day: 2462 kg
300 repetitions/day: 2268 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4000 kg
The Dynamic load for:
50 repetitions/day: 3210 kg
100 repetitions/day: 2950 kg
200 repetitions/day: 2649 kg
300 repetitions/day: 2465 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m – 5m
Outdoor slab: 3,5m – 4m
Depth of cut joint: 5,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 3895 kg
The Dynamic load for:
50 repetitions/day: 3150 kg
100 repetitions/day: 2920 kg
200 repetitions/day: 2620 kg
300 repetitions/day: 2400 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 6 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4133 kg
The Dynamic load for:
50 repetitions/day: 3400 kg
100 repetitions/day: 3140 kg
200 repetitions/day: 2810 kg
300 repetitions/day: 2600 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m – 5m
Outdoor slab: 3,5m – 4m
Depth of cut joint: 6 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4100 kg
The Dynamic load for:
50 repetitions/day: 3307 kg
100 repetitions/day: 3070 kg
200 repetitions/day: 2742 kg
300 repetitions/day: 2525 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 6 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4350 kg
The Dynamic load for:
50 repetitions/day: 3572 kg
100 repetitions/day: 3290 kg
200 repetitions/day: 2940 kg
300 repetitions/day: 2723 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m – 5m
Outdoor slab: 3,5m – 4m
Depth of cut joint: 6 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4275 kg
The Dynamic load for:
50 repetitions/day: 3470 kg
100 repetitions/day: 3200 kg
200 repetitions/day: 2860 kg
300 repetitions/day: 2660 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4513 kg
The Dynamic load for:
50 repetitions/day: 3750 kg
100 repetitions/day: 3465 kg
200 repetitions/day: 3100 kg
300 repetitions/day: 2875 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m – 5,5m
Outdoor slab: 4m – 5m
Depth of cut joint: 6 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4500 kg
The Dynamic load for:
50 repetitions/day: 3640 kg
100 repetitions/day: 3355 kg
200 repetitions/day: 3007 kg
300 repetitions/day: 2790 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4750 kg
The Dynamic load for:
50 repetitions/day: 3930 kg
100 repetitions/day: 3641 kg
200 repetitions/day: 3248 kg
300 repetitions/day: 3020 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m – 5,5m
Outdoor slab: 4m – 5m
Depth of cut joint: 6 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4655 kg
The Dynamic load for:
50 repetitions/day: 3800 kg
100 repetitions/day: 3500 kg
200 repetitions/day: 3140 kg
300 repetitions/day: 2910 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4940 kg
The Dynamic load for:
50 repetitions/day: 4120 kg
100 repetitions/day: 3810 kg
200 repetitions/day: 3410 kg
300 repetitions/day: 3160 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m – 5,5m
Outdoor slab: 4m – 5m
Depth of cut joint: 6,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4900 kg
The Dynamic load for:
50 repetitions/day: 3960 kg
100 repetitions/day: 33680 kg
200 repetitions/day: 3300 kg
300 repetitions/day: 3047 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5200 kg
The Dynamic load for:
50 repetitions/day: 4330 kg
100 repetitions/day: 3986 kg
200 repetitions/day: 3583 kg
300 repetitions/day: 3325 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m – 5,5m
Outdoor slab: 4m – 5m
Depth of cut joint: 6,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5035 kg
The Dynamic load for:
50 repetitions/day: 4150 kg
100 repetitions/day: 3840 kg
200 repetitions/day: 3430 kg
300 repetitions/day: 3180 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4m - 5m
Depth of cut joint: 7 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5415 kg
The Dynamic load for:
50 repetitions/day: 4510 kg
100 repetitions/day: 4170 kg
200 repetitions/day: 3730 kg
300 repetitions/day: 3465 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m – 6m
Outdoor slab: 4m – 5m
Depth of cut joint: 7 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5300 kg
The Dynamic load for:
50 repetitions/day: 4350 kg
100 repetitions/day: 4030 kg
200 repetitions/day: 3580 kg
300 repetitions/day: 3325 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4m - 5m
Depth of cut joint: 7 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5700 kg
The Dynamic load for:
50 repetitions/day: 4730 kg
100 repetitions/day: 4370 kg
200 repetitions/day: 3900 kg
300 repetitions/day: 3642 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m – 6m
Outdoor slab: 4m – 5m
Depth of cut joint: 7 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5463 kg
The Dynamic load for:
50 repetitions/day: 4530 kg
100 repetitions/day: 4180 kg
200 repetitions/day: 3740 kg
300 repetitions/day: 3470 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5890 kg
The Dynamic load for:
50 repetitions/day: 4925 kg
100 repetitions/day: 4550 kg
200 repetitions/day: 4065 kg
300 repetitions/day: 3775 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m – 6m
Outdoor slab: 4,5m – 6m
Depth of cut joint: 7 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5750 kg
The Dynamic load for:
50 repetitions/day: 4750 kg
100 repetitions/day: 4365 kg
200 repetitions/day: 3920 kg
300 repetitions/day: 3660 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6200 kg
The Dynamic load for:
50 repetitions/day: 5168 kg
100 repetitions/day: 4780 kg
200 repetitions/day: 4275 kg
300 repetitions/day: 3950 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m – 6m
Outdoor slab: 4,5m – 6m
Depth of cut joint: 7 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6033 kg
The Dynamic load for:
50 repetitions/day: 4920 kg
100 repetitions/day: 4540 kg
200 repetitions/day: 4070 kg
300 repetitions/day: 3765 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6365 kg
The Dynamic load for:
50 repetitions/day: 4925 kg
100 repetitions/day: 4550 kg
200 repetitions/day: 4065 kg
300 repetitions/day: 3775 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m – 6,5m
Outdoor slab: 4,5m – 6m
Depth of cut joint: 7,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6350 kg
The Dynamic load for:
50 repetitions/day: 5160 kg
100 repetitions/day: 4755 kg
200 repetitions/day: 4260 kg
300 repetitions/day: 3970 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 3m
Depth of cut joint: 7,5 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6700 kg
The Dynamic load for:
50 repetitions/day: 5168 kg
100 repetitions/day: 4780 kg
200 repetitions/day: 4275 kg
300 repetitions/day: 3950 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m – 6,5m
Outdoor slab: 4,5m – 6m
Depth of cut joint: 7,5 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6413 kg
The Dynamic load for:
50 repetitions/day: 5320 kg
100 repetitions/day: 4910 kg
200 repetitions/day: 4400 kg
300 repetitions/day: 4080 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 8 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6793 kg
The Dynamic load for:
50 repetitions/day: 5790 kg
100 repetitions/day: 5340 kg
200 repetitions/day: 4780 kg
300 repetitions/day: 4440 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m – 6,5m
Outdoor slab: 4,5m – 6m
Depth of cut joint: 8 cm

CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6750 kg
The Dynamic load for:
50 repetitions/day: 5585 kg
100 repetitions/day: 5145 kg
200 repetitions/day: 4630 kg
300 repetitions/day: 4300 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6ma
Depth of cut joint: 8 cm

CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 7150 kg
The Dynamic load for:
50 repetitions/day: 6070 kg
100 repetitions/day: 5590 kg
200 repetitions/day: 5002 kg
300 repetitions/day: 4670 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m – 6,5m
Outdoor slab: 4,5m – 6m
Depth of cut joint: 8 cm