k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 3990 kg
The Dynamic load for:
50 repetitions/day: 2410 kg
100 repetitions/day: 2225 kg
200 repetitions/day: 1990 kg
300 repetitions/day: 1840 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 3990 kg
The Dynamic load for:
50 repetitions/day: 2615 kg
100 repetitions/day: 2415 kg
200 repetitions/day: 2165 kg
300 repetitions/day: 2010 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4750 kg
The Dynamic load for:
50 repetitions/day: 2700 kg
100 repetitions/day: 2470 kg
200 repetitions/day: 2230 kg
300 repetitions/day: 2065 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4750 kg
The Dynamic load for:
50 repetitions/day: 2930 kg
100 repetitions/day: 2700 kg
200 repetitions/day: 2420 kg
300 repetitions/day: 2240 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4200 kg
The Dynamic load for:
50 repetitions/day: 2520 kg
100 repetitions/day: 2328 kg
200 repetitions/day: 2070 kg
300 repetitions/day: 1920 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m4
Depth of cut joint: 4 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4200 kg
The Dynamic load for:
50 repetitions/day: 2740 kg
100 repetitions/day: 2520 kg
200 repetitions/day: 2250 kg
300 repetitions/day: 2100 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m4
Depth of cut joint: 4 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5000 kg
The Dynamic load for:
50 repetitions/day: 2830 kg
100 repetitions/day: 2580 kg
200 repetitions/day: 2350 kg
300 repetitions/day: 2155 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m4
Depth of cut joint: 4 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 12 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5000 kg
The Dynamic load for:
50 repetitions/day: 3050 kg
100 repetitions/day: 2800 kg
200 repetitions/day: 2550 kg
300 repetitions/day: 2340 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m4
Depth of cut joint: 4 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4370 kg
The Dynamic load for:
50 repetitions/day: 2730 kg
100 repetitions/day: 2510 kg
200 repetitions/day: 2250 kg
300 repetitions/day: 2090 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4370 kg
The Dynamic load for:
50 repetitions/day: 2960 kg
100 repetitions/day: 2740 kg
200 repetitions/day: 2450 kg
300 repetitions/day: 2270 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5178 kg
The Dynamic load for:
50 repetitions/day: 3030 kg
100 repetitions/day: 2800 kg
200 repetitions/day: 2500 kg
300 repetitions/day: 2320 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5178 kg
The Dynamic load for:
50 repetitions/day: 3300 kg
100 repetitions/day: 3040 kg
200 repetitions/day: 2720 kg
300 repetitions/day: 2530 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4600 kg
The Dynamic load for:
50 repetitions/day: 2850 kg
100 repetitions/day: 2610 kg
101 repetitions/day: 2330 kg
300 repetitions/day: 2165 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m
Depth of cut joint: 4 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 4600 kg
The Dynamic load for:
50 repetitions/day: 3100 kg
100 repetitions/day: 2850 kg
200 repetitions/day: 2570 kg
300 repetitions/day: 2360 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m4
Depth of cut joint: 4 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5450 kg
The Dynamic load for:
50 repetitions/day: 3170 kg
100 repetitions/day: 2930 kg
200 repetitions/day: 2630 kg
300 repetitions/day: 2440 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m4
Depth of cut joint: 4 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 13 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5450 kg
The Dynamic load for:
50 repetitions/day: 3450 kg
100 repetitions/day: 3185 kg
200 repetitions/day: 2860 kg
300 repetitions/day: 2650 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3m - 3,5m
Outdoor slab: 2m - 3m4
Depth of cut joint: 4 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4845 kg
The Dynamic load for:
50 repetitions/day: 3060 kg
100 repetitions/day: 2830 kg
200 repetitions/day: 2530 kg
300 repetitions/day: 2340 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m - 4m
Outdoor slab: 2,5m - 3,5m
Depth of cut joint: 4,5 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 4845 kg
The Dynamic load for:
50 repetitions/day: 3320 kg
100 repetitions/day: 3070 kg
200 repetitions/day: 2750 kg
300 repetitions/day: 2550 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m - 4m
Outdoor slab: 2,5m - 3,5m
Depth of cut joint: 4,5 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5700 kg
The Dynamic load for:
50 repetitions/day: 3380 kg
100 repetitions/day: 3120 kg
200 repetitions/day: 2800 kg
300 repetitions/day: 2600 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m - 4m
Outdoor slab: 2,5m - 3,5m
Depth of cut joint: 4,5 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5700 kg
The Dynamic load for:
50 repetitions/day: 3680 kg
100 repetitions/day: 3400 kg
200 repetitions/day: 3040 kg
300 repetitions/day: 2820 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m - 4m
Outdoor slab: 2,5m - 3,5m
Depth of cut joint: 4,5 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5100 kg
The Dynamic load for:
50 repetitions/day: 3200 kg
100 repetitions/day: 2950 kg
200 repetitions/day: 2640 kg
300 repetitions/day: 2410 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m - 4m
Outdoor slab: 2,5m - 3,5m4,5
Depth of cut joint: 4,5 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5100 kg
The Dynamic load for:
50 repetitions/day: 3470 kg
100 repetitions/day: 3220 kg
200 repetitions/day: 2870 kg
300 repetitions/day: 2660 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m - 4m
Outdoor slab: 2,5m - 3,5m4,5
Depth of cut joint: 4,5 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6000 kg
The Dynamic load for:
50 repetitions/day: 2530 kg
100 repetitions/day: 3270 kg
200 repetitions/day: 2950 kg
300 repetitions/day: 2735 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m - 4m
Outdoor slab: 2,5m - 3,5m4,5
Depth of cut joint: 4,5 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 14 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6000 kg
The Dynamic load for:
50 repetitions/day: 3860 kg
100 repetitions/day: 3560 kg
200 repetitions/day: 3200 kg
300 repetitions/day: 2970 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,5m - 4m
Outdoor slab: 2,5m - 3,5m4,5
Depth of cut joint: 4,5 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5368 kg
The Dynamic load for:
50 repetitions/day: 3410 kg
100 repetitions/day: 3150 kg
200 repetitions/day: 2820 kg
300 repetitions/day: 2610 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5368 kg
The Dynamic load for:
50 repetitions/day: 3710 kg
100 repetitions/day: 3420 kg
200 repetitions/day: 3070 kg
300 repetitions/day: 2850 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6175 kg
The Dynamic load for:
50 repetitions/day: 3760 kg
100 repetitions/day: 3470 kg
200 repetitions/day: 3110 kg
300 repetitions/day: 2880 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6175 kg
The Dynamic load for:
50 repetitions/day: 4080 kg
100 repetitions/day: 3770 kg
200 repetitions/day: 3380 kg
300 repetitions/day: 3130 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5650 kg
The Dynamic load for:
50 repetitions/day: 3560 kg
100 repetitions/day: 3300 kg
200 repetitions/day: 2950 kg
300 repetitions/day: 2725 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m5
Depth of cut joint: 5 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 5650 kg
The Dynamic load for:
50 repetitions/day: 3880 kg
100 repetitions/day: 3585 kg
200 repetitions/day: 3230 kg
300 repetitions/day: 3000 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m5
Depth of cut joint: 5 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6500 kg
The Dynamic load for:
50 repetitions/day: 3935 kg
100 repetitions/day: 3640 kg
200 repetitions/day: 3270 kg
300 repetitions/day: 3030 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m5
Depth of cut joint: 5 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 15 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6500 kg
The Dynamic load for:
50 repetitions/day: 4280 kg
100 repetitions/day: 3950 kg
200 repetitions/day: 3560 kg
300 repetitions/day: 3300 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m5
Depth of cut joint: 5 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5890 kg
The Dynamic load for:
50 repetitions/day: 3785 kg
100 repetitions/day: 3490 kg
200 repetitions/day: 3130 kg
300 repetitions/day: 2900 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 5890 kg
The Dynamic load for:
50 repetitions/day: 4110 kg
100 repetitions/day: 3800 kg
200 repetitions/day: 3400 kg
300 repetitions/day: 3150 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6745 kg
The Dynamic load for:
50 repetitions/day: 4150 kg
100 repetitions/day: 3830 kg
200 repetitions/day: 3440 kg
300 repetitions/day: 3180 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6745 kg
The Dynamic load for:
50 repetitions/day: 4510 kg
100 repetitions/day: 4160 kg
200 repetitions/day: 3730 kg
300 repetitions/day: 3460 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6200 kg
The Dynamic load for:
50 repetitions/day: 3950 kg
100 repetitions/day: 3625 kg
200 repetitions/day: 3280 kg
300 repetitions/day: 3050 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m5
Depth of cut joint: 5 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6200 kg
The Dynamic load for:
50 repetitions/day: 4300 kg
100 repetitions/day: 4010 kg
200 repetitions/day: 3560 kg
300 repetitions/day: 3310 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m5
Depth of cut joint: 5 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 7100 kg
The Dynamic load for:
50 repetitions/day: 4350 kg
100 repetitions/day: 4000 kg
200 repetitions/day: 3600 kg
300 repetitions/day: 3340 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m5
Depth of cut joint: 5 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 16 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 7100 kg
The Dynamic load for:
50 repetitions/day: 4700 kg
100 repetitions/day: 4370 kg
200 repetitions/day: 3900 kg
300 repetitions/day: 3615 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 3,75m- 4,5m
Outdoor slab: 3,5m - 4m5
Depth of cut joint: 5 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6460 kg
The Dynamic load for:
50 repetitions/day: 4180 kg
100 repetitions/day: 3850 kg
200 repetitions/day: 3450 kg
300 repetitions/day: 3200 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5,5 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 6460 kg
The Dynamic load for:
50 repetitions/day: 4550 kg
100 repetitions/day: 4200 kg
200 repetitions/day: 3750 kg
300 repetitions/day: 3480 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5,5 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 7315 kg
The Dynamic load for:
50 repetitions/day: 4560 kg
100 repetitions/day: 4210 kg
200 repetitions/day: 3770 kg
300 repetitions/day: 3500 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5,5 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 7315 kg
The Dynamic load for:
50 repetitions/day: 4960 kg
100 repetitions/day: 4570 kg
200 repetitions/day: 4100 kg
300 repetitions/day: 3800 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 5,5 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6800 kg
The Dynamic load for:
50 repetitions/day: 4360 kg
100 repetitions/day: 4035 kg
200 repetitions/day: 3600 kg
300 repetitions/day: 3350 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m5,5
Depth of cut joint: 5,5 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 6800 kg
The Dynamic load for:
50 repetitions/day: 4750 kg
100 repetitions/day: 4400 kg
200 repetitions/day: 3910 kg
300 repetitions/day: 3640 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m5,5
Depth of cut joint: 5,5 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 7700 kg
The Dynamic load for:
50 repetitions/day: 4780 kg
100 repetitions/day: 4435 kg
200 repetitions/day: 3945 kg
300 repetitions/day: 3650 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m5,5
Depth of cut joint: 5,5 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 17 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 7700 kg
The Dynamic load for:
50 repetitions/day: 5200 kg
100 repetitions/day: 4780 kg
200 repetitions/day: 4300 kg
300 repetitions/day: 4000 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m5,5
Depth of cut joint: 5,5 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 7030 kg
The Dynamic load for:
50 repetitions/day: 4580 kg
100 repetitions/day: 4230 kg
200 repetitions/day: 3785 kg
300 repetitions/day: 3510 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 6 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 7030 kg
The Dynamic load for:
50 repetitions/day: 4980 kg
100 repetitions/day: 4600 kg
200 repetitions/day: 4110 kg
300 repetitions/day: 3810 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 6 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 7933 kg
The Dynamic load for:
50 repetitions/day: 5000 kg
100 repetitions/day: 4600 kg
200 repetitions/day: 4130 kg
300 repetitions/day: 3820 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 6 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 7933 kg
The Dynamic load for:
50 repetitions/day: 5420 kg
100 repetitions/day: 5000 kg
200 repetitions/day: 4500 kg
300 repetitions/day: 4150 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m
Depth of cut joint: 6 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 7400 kg
The Dynamic load for:
50 repetitions/day: 4800 kg
100 repetitions/day: 4425 kg
200 repetitions/day: 3950 kg
300 repetitions/day: 3680 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m6
Depth of cut joint: 6 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 7400 kg
The Dynamic load for:
50 repetitions/day: 5210 kg
100 repetitions/day: 4820 kg
200 repetitions/day: 4300 kg
300 repetitions/day: 3810 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m6
Depth of cut joint: 6 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 8350 kg
The Dynamic load for:
50 repetitions/day: 5240 kg
100 repetitions/day: 4840 kg
200 repetitions/day: 4330 kg
300 repetitions/day: 4000 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m6
Depth of cut joint: 6 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 18 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 8350 kg
The Dynamic load for:
50 repetitions/day: 5675 kg
100 repetitions/day: 52552550 kg
200 repetitions/day: 4720 kg
300 repetitions/day: 4370 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4m - 5m
Outdoor slab: 3,5m - 4m6
Depth of cut joint: 6 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 7600 kg
The Dynamic load for:
50 repetitions/day: 5000 kg
100 repetitions/day: 4620 kg
200 repetitions/day: 4140 kg
300 repetitions/day: 3840 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 7600 kg
The Dynamic load for:
50 repetitions/day: 5440 kg
100 repetitions/day: 5020 kg
200 repetitions/day: 4500 kg
300 repetitions/day: 4170 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 8550 kg
The Dynamic load for:
50 repetitions/day: 5430 kg
100 repetitions/day: 5020 kg
200 repetitions/day: 4500 kg
300 repetitions/day: 4170 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 8550 kg
The Dynamic load for:
50 repetitions/day: 5900 kg
100 repetitions/day: 5450 kg
200 repetitions/day: 4880 kg
300 repetitions/day: 4530 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 8000 kg
The Dynamic load for:
50 repetitions/day: 5230 kg
100 repetitions/day: 4850 kg
200 repetitions/day: 4305 kg
300 repetitions/day: 4010 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m6
Depth of cut joint: 6 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 8000 kg
The Dynamic load for:
50 repetitions/day: 5700 kg
100 repetitions/day: 5250 kg
200 repetitions/day: 4700 kg
300 repetitions/day: 4350 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m6
Depth of cut joint: 6 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 9000 kg
The Dynamic load for:
50 repetitions/day: 5710 kg
100 repetitions/day: 5250 kg
200 repetitions/day: 4730 kg
300 repetitions/day: 4380 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m6
Depth of cut joint: 6 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 19 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 9000 kg
The Dynamic load for:
50 repetitions/day: 6180 kg
100 repetitions/day: 5700 kg
200 repetitions/day: 5120 kg
300 repetitions/day: 4770 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m6
Depth of cut joint: 6 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 8265 kg
The Dynamic load for:
50 repetitions/day: 5440 kg
100 repetitions/day: 5040 kg
200 repetitions/day: 4500 kg
300 repetitions/day: 4175 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6,5 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 8265 kg
The Dynamic load for:
50 repetitions/day: 5920 kg
100 repetitions/day: 5460 kg
200 repetitions/day: 4890 kg
300 repetitions/day: 4540 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6,5 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 9215 kg
The Dynamic load for:
50 repetitions/day: 5900 kg
100 repetitions/day: 5450 kg
200 repetitions/day: 4880 kg
300 repetitions/day: 4520 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6,5 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 9215 kg
The Dynamic load for:
50 repetitions/day: 6410 kg
100 repetitions/day: 5900 kg
200 repetitions/day: 5300 kg
300 repetitions/day: 4910 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m
Depth of cut joint: 6,5 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 8700 kg
The Dynamic load for:
50 repetitions/day: 5700 kg
100 repetitions/day: 5250 kg
200 repetitions/day: 4700 kg
300 repetitions/day: 4360 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m6,5
Depth of cut joint: 6,5 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 8700 kg
The Dynamic load for:
50 repetitions/day: 6200 kg
100 repetitions/day: 5700 kg
200 repetitions/day: 5120 kg
300 repetitions/day: 4750 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m6,5
Depth of cut joint: 6,5 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 9700 kg
The Dynamic load for:
50 repetitions/day: 6180 kg
100 repetitions/day: 5700 kg
200 repetitions/day: 5120 kg
300 repetitions/day: 4750 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m6,5
Depth of cut joint: 6,5 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 20 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 9700 kg
The Dynamic load for:
50 repetitions/day: 6700 kg
100 repetitions/day: 6200 kg
200 repetitions/day: 5550 kg
300 repetitions/day: 5150 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,25m - 5,5m
Outdoor slab: 4m - 5m6,5
Depth of cut joint: 6,5 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 8883 kg
The Dynamic load for:
50 repetitions/day: 5910 kg
100 repetitions/day: 5450 kg
200 repetitions/day: 4880 kg
300 repetitions/day: 4530 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4m - 5m
Depth of cut joint: 7 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 8883 kg
The Dynamic load for:
50 repetitions/day: 6420 kg
100 repetitions/day: 5930 kg
200 repetitions/day: 5310 kg
300 repetitions/day: 4920 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4m - 5m
Depth of cut joint: 7 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 9880 kg
The Dynamic load for:
50 repetitions/day: 6400 kg
100 repetitions/day: 5900 kg
200 repetitions/day: 5300 kg
300 repetitions/day: 4900 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4m - 5m
Depth of cut joint: 7 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 9880 kg
The Dynamic load for:
50 repetitions/day: 6940 kg
100 repetitions/day: 6400 kg
200 repetitions/day: 5740 kg
300 repetitions/day: 5315 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4m - 5m
Depth of cut joint: 7 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 9350 kg
The Dynamic load for:
50 repetitions/day: 6200 kg
100 repetitions/day: 5700 kg
200 repetitions/day: 5105 kg
300 repetitions/day: 4760 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4m - 5m7
Depth of cut joint: 7 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 9350 kg
The Dynamic load for:
50 repetitions/day: 6720 kg
100 repetitions/day: 6200 kg
200 repetitions/day: 5560 kg
300 repetitions/day: 5150 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4m - 5m7
Depth of cut joint: 7 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 10400 kg
The Dynamic load for:
50 repetitions/day: 6700 kg
100 repetitions/day: 6200 kg
200 repetitions/day: 5555 kg
300 repetitions/day: 5150 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4m - 5m7
Depth of cut joint: 7 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 21 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 10400 kg
The Dynamic load for:
50 repetitions/day: 7300 kg
100 repetitions/day: 6700 kg
200 repetitions/day: 5980 kg
300 repetitions/day: 5600 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4m - 5m7
Depth of cut joint: 7 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 9595 kg
The Dynamic load for:
50 repetitions/day: 6400 kg
100 repetitions/day: 5900 kg
200 repetitions/day: 5280 kg
300 repetitions/day: 4900 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 9595 kg
The Dynamic load for:
50 repetitions/day: 6940 kg
100 repetitions/day: 6400 kg
200 repetitions/day: 5740 kg
300 repetitions/day: 5320 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 10593 kg
The Dynamic load for:
50 repetitions/day: 6900 kg
100 repetitions/day: 6350 kg
200 repetitions/day: 5700 kg
300 repetitions/day: 5280 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 10593 kg
The Dynamic load for:
50 repetitions/day: 7480 kg
100 repetitions/day: 6900 kg
200 repetitions/day: 6200 kg
300 repetitions/day: 5750 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 10100 kg
The Dynamic load for:
50 repetitions/day: 6700 kg
100 repetitions/day: 6160 kg
200 repetitions/day: 5550 kg
300 repetitions/day: 5120 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4,5m - 6m7
Depth of cut joint: 7 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 10100 kg
The Dynamic load for:
50 repetitions/day: 7260 kg
100 repetitions/day: 6710 kg
200 repetitions/day: 6005 kg
300 repetitions/day: 5550 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4,5m - 6m7
Depth of cut joint: 7 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 11150 kg
The Dynamic load for:
50 repetitions/day: 7220 kg
100 repetitions/day: 6660 kg
200 repetitions/day: 5965 kg
300 repetitions/day: 5550 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4,5m - 6m7
Depth of cut joint: 7 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 22 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 11150 kg
The Dynamic load for:
50 repetitions/day: 7810 kg
100 repetitions/day: 7255 kg
200 repetitions/day: 6550 kg
300 repetitions/day: 5980 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,5m - 6m
Outdoor slab: 4,5m - 6m7
Depth of cut joint: 7 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 10260 kg
The Dynamic load for:
50 repetitions/day: 6900 kg
100 repetitions/day: 6350 kg
200 repetitions/day: 5700 kg
300 repetitions/day: 5270 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7,5 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 10260 kg
The Dynamic load for:
50 repetitions/day: 7480 kg
100 repetitions/day: 6900 kg
200 repetitions/day: 6200 kg
300 repetitions/day: 5740 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7,5 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 11305 kg
The Dynamic load for:
50 repetitions/day: 7400 kg
100 repetitions/day: 6840 kg
200 repetitions/day: 6120 kg
300 repetitions/day: 5670 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7,5 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 11305 kg
The Dynamic load for:
50 repetitions/day: 8040 kg
100 repetitions/day: 7430 kg
200 repetitions/day: 6650 kg
300 repetitions/day: 6170 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 7,5 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 10800 kg
The Dynamic load for:
50 repetitions/day: 7210 kg
100 repetitions/day: 6660 kg
200 repetitions/day: 5970 kg
300 repetitions/day: 5510 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m7,5
Depth of cut joint: 7,5 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 10800 kg
The Dynamic load for:
50 repetitions/day: 7840 kg
100 repetitions/day: 7230 kg
200 repetitions/day: 6500 kg
300 repetitions/day: 6015 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m7,5
Depth of cut joint: 7,5 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 11900 kg
The Dynamic load for:
50 repetitions/day: 7750 kg
100 repetitions/day: 7150 kg
200 repetitions/day: 6400 kg
300 repetitions/day: 5950 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m7,5
Depth of cut joint: 7,5 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 23 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 11900 kg
The Dynamic load for:
50 repetitions/day: 8440 kg
100 repetitions/day: 7820 kg
200 repetitions/day: 6950 kg
300 repetitions/day: 6500 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m7,5
Depth of cut joint: 7,5 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 10973 kg
The Dynamic load for:
50 repetitions/day: 7385 kg
100 repetitions/day: 6820 kg
200 repetitions/day: 6120 kg
300 repetitions/day: 5660 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 8 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 10973 kg
The Dynamic load for:
50 repetitions/day: 8030 kg
100 repetitions/day: 7380 kg
200 repetitions/day: 6650 kg
300 repetitions/day: 6150 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 8 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 12065 kg
The Dynamic load for:
50 repetitions/day: 7940 kg
100 repetitions/day: 7340 kg
200 repetitions/day: 6570 kg
300 repetitions/day: 6100 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 8 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 2 kg / m³
The maximum permisible static point load is 12065 kg
The Dynamic load for:
50 repetitions/day: 8620 kg
100 repetitions/day: 7960 kg
200 repetitions/day: 7150 kg
300 repetitions/day: 6620 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 8 cm

k=5 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 11550 kg
The Dynamic load for:
50 repetitions/day: 7750 kg
100 repetitions/day: 7145 kg
200 repetitions/day: 6400 kg
300 repetitions/day: 5920 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m8
Depth of cut joint: 8 cm

k=5 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 11550 kg
The Dynamic load for:
50 repetitions/day: 8400 kg
100 repetitions/day: 7720 kg
200 repetitions/day: 6950 kg
300 repetitions/day: 6450 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m8
Depth of cut joint: 8 cm

k=10 kg/cm³ | CONCRETE C25 – 25 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 12700 kg
The Dynamic load for:
50 repetitions/day: 8300 kg
100 repetitions/day: 7700 kg
200 repetitions/day: 6850 kg
300 repetitions/day: 6400 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 8 cm

k=10 kg/cm³ | CONCRETE C30 – 30 N/mm²

SLAB THICKNESS 24 cm

DOSAGE SUPER FIBRA BIGMAT AR: 3 kg / m³
The maximum permisible static point load is 12700 kg
The Dynamic load for:
50 repetitions/day: 9010 kg
100 repetitions/day: 8300 kg
200 repetitions/day: 7500 kg
300 repetitions/day: 6980 kg
The recommended distances between the shrinkage joints are:
Indoor slab: 4,75m - 6,5m
Outdoor slab: 4,5m - 6m
Depth of cut joint: 8 cm